Grey Water Treatment Plant: Process Description
- The outfall sewer main from the last manholes will be let into a screen by gravity flow. Large solids particles shall be intercepted by a 5 mm – 8 mm spacing screen. The screen shall be manually cleaned with suitable rake arrangement.
- The Grey Water after the screening is collected in a collection sump for smoothing out peak flows. This sump is suitably sized, to accommodate peak flow, as well as breakdown buffer. The provision of the air shall be kept in this tank to break the solids in suspension and to homogenize the Grey Water.
- The homogenized grey water is then pumped into the Aeration Basin. The air shall be provided through an air diffusion system to ensure equal distribution of air in the reactor.
- The overflow from the Aeration basin is passed through a Settler, and collected in Clarified Tank by gravity& Here Sodium hypochlorite added for disinfection, from where it is pumped to a pressure sand filter, which is capable of removing finely divided colloidal particles. An activated carbon filter will remove all traces of color and odor so that the grey water can be used for gardening/flushing/irrigation.
- Filter backwash and sludge filtrate would be taken back into the collection sump.
- Sludge generated in the Settler will be de-watered in a sludge holding tank/sludge drying bed. This sludge can be used as organic manure and sold as such.
- Excess treated grey water can be discharged into the sewer or used as per requirement since it meets PCB requirements.